Features & Benefits
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Optional ΔT and temperature return limitation
Optimize the efficiency of your production units by ensuring optimal temperature regimes.
Change-over functionality
Switch between heating/cooling flows according to input signal or automatically using T supply or ΔT sign detection.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly.
Quick copying of settings
Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.
Technical Information
Functions:
Proportional control
Manual override (TA-Dongle)
Stroke detection
Mode, status and position indication
Stroke limitation setting
Minimum stroke setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging
Delayed start-up
ΔT and temperature return limitation
Reading (supply/return temperature, ΔT, position)
Automatic change-over function
T version:
+ 1 pre-mounted PT1000 to be inserted in valve measuring point.
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ Output signal
2T version:
+ 1 pre-mounted cable with possibility to connect 2 PT1000 (see section “Sensors”)
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ Output signal
Supply voltage:
24 VAC/VDC ±15%.
Frequency 50/60 Hz ±3 Hz.
Power consumption:
Operation: < 3.6 VA (VAC); < 1.7 W (VDC)
Standby: < 1.3 VA (VAC); < 0.6 W (VDC)
Input signal:
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC.
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
2-6, 6-2, 6-10 or 10-6 VDC.
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC,
2-4.7 / 7.3-10 VDC,
0-4.5 / 5.5-10 VDC or
2-5.5 / 6.5-10 VDC.
Default setting: Proportional 0-10 VDC.
Output signal:
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Ranges: See “Input signal”.
Default setting: Proportional 0-10 VDC.
Characteristics:
Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.
Control speed:
4 or 6 s/mm.
Default setting: 4 s/mm.
Adjusting force:
Push 500 N
Pull 300 N
Temperature:
Media temperature: max. 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Measurement accuracy:
Temperature pocket: Class AA
In valve measuring point: Class B
Surface mounted: Class B
Absolute temperature:
PT1000 Class AA: ±0.1°C at 0°C
PT1000 Class B: ±0.3°C at 0°C
Time constant τ (63%):
In valve measuring point: 5s
Temperature pocket: 9s
Surface mounted: 20s
Ingress protection:
IP54
all directions
(according to EN 60529)
Protection class:
(according to EN 61140)
III (SELV)
Cable:
1, 2 or 5 m.
Halogen free with wire end sleeves.
Fire class B2ca – s1a, d1, a1 according to EN 50575.
Type LiYY, 5x0.25 mm2.
Temperature sensor cable:
Halogen free, fire class IEC 60332-3-24 (cat. C).
T version: Length 160 mm.
2T version: Length, see section “Sensors”.
Stroke:
16,2 mm
Noise level:
Max. 30 dBA
Weight:
TA-Slider 500 T:
0.29 kg, 1 m cable
0.34 kg, 2 m cable
0.49 kg, 5 m cable
TA-Slider 500 2T:
0.34 kg, 1 m cable
0.39 kg, 2 m cable
0.54 kg, 5 m cable
Connection to valve:
Swivelling nut M30x1,5.
Material:
Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.
Cables: Halogen free
Colour:
White RAL 9016, grey RAL 7047.
Marking:
Label: IMI TA, CE, product name, article No. and technical specification.
Certification CE:
LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000.
Product standard:
EN 60730
Articles
Without pre-mounted PT1000. Sensors ordered separately.
TA-Slider 500 2T
Without pre-mounted PT1000. Sensors ordered separately.
Input signal: 0(2)-10 VDC
Cable length | Sensor cable length | Supply voltage | EAN | Article No |
1000 | 1000 | 24 VAC/VDC | 5902276820922 | 322225-10914 |
2000 | 1000 | 24 VAC/VDC | 5902276820939 | 322225-10915 |
5000 | 1000 | 24 VAC/VDC | 5902276820946 | 322225-10916 |
Pre-mounted PT1000 for valve measuring point insertion.
TA-Slider 500 T
Pre-mounted PT1000 for valve measuring point insertion.
Input signal: 0(2)-10 VDC
Cable length | Sensor cable length | Supply voltage | EAN | Article No |
1000 | 160 | 24 VAC/VDC | 5902276820892 | 322225-10814 |
2000 | 160 | 24 VAC/VDC | 5902276820908 | 322225-10815 |
5000 | 160 | 24 VAC/VDC | 5902276820915 | 322225-10816 |
PT1000For mounting directly on pipe surface.
Surface temperature sensor
PT1000
For mounting directly on pipe surface.
H | L | Cable length | EAN | Article No |
10 | 16 | 3000 | 5902276820816 | 322428-00429 |
PT1000For mounting directly on pipe. Free space >70 mm is required above the temperature sensor pocket.
Temperature pocket with sensor
PT1000
For mounting directly on pipe.
Free space >70 mm is required above the temperature sensor pocket.
For pipe DN | d | L | Cable length | EAN | Article No |
10-25 | G1/2 | 25 | 3000 | 5902276820748 | 322428-00020 |
32-50 | G1/2 | 40 | 3000 | 5902276820755 | 322428-00521 |
65-80 | G1/2 | 70 | 3000 | 5902276821745 | 322428-00621 |
100-400 | G1/2 | 100 | 3000 | 5902276821738 | 322428-00721 |
PT1000Applicable to families: TA-Modulator, TBV-CM, TA-COMPACT-P/-DP, STAD, STAF/STAF-SG
Temperature sensor for valve measuring point
PT1000
Applicable to families: TA-Modulator, TBV-CM, TA-COMPACT-P/-DP, STAD, STAF/STAF-SG
For valve DN | L | Cable length | EAN | Article No |
10-50 | 60 | 3000 | 5902276820786 | 322428-00122 |
65-250 | 130 | 5000 | 5902276820793 | 322428-00134 |
300-400 + STAF 150 | 170 | 5000 | 5902276820809 | 322428-00135 |
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.
TA-Dongle
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.
EAN | Article No |
5901688828632 | 322228-00001 |